Click
here for PDF Version
INTRODUCTION

|
Figure
1. Selkirk Twin Homes, Grand Forks, ND |
The
Eastern Dakota Housing Alliance has completed 8 of 20 planned
multi-family and single-family dwellings on Selkirk Circle in
Grand Forks, North Dakota. Four twin-home (duplex) units were
completed in March of 2003 (Phase I) and four more identical
units were completed in February of 2004 (Phase II). Four additional
units (Phase III) are due for completion by mid-summer, 2004.
Design assistance and performance testing were provided by the
Building America Industrialized Housing Project with the goal
of achieving up to 50% energy savings over the 1993 Model Energy
Code.
To
approach this level of savings, various envelope and equipment
upgrades were assessed through DOE 2 computer simulations. Base
case, Phase I and Phase II homes were modeled including input
from envelope and duct leakage testing. Annual combined gas and
electric utility savings estimates ranged from 25% on Phase I
homes to 35% on Phase II homes over the base case unit built
to local minimum standards. A cost comparison of standard and
improved systems was also performed.
 |
| Figure
2. Twin Home Unit
|
The
use of Extruded Polystyrene (XPS) rigid foam sheathing and tankless
gas water heaters were two features, considered innovative by
local standards, providing much of the increased energy savings
of the Phase II homes over Phase I. The decision to use insulated
sheathing was driven by a tripling in the price of plywood during
the summer of 2003, making it comparable to the price of R-10
XPS foam. Whole house tankless gas water heaters, far more popular
overseas than in the U.S., were costly to purchase and install
compared to typical gas or electric choices, but provide substantial
savings. The size of a small suitcase, these units saved valuable
space in the compact Selkirk home design and are claimed to last
20 years or more.
Building
Simulation Software
The
software called EnergyGauge USA® (Parker et al. 1999), provides
an input interface for performing hourly computations with the
DOE2.1E simulation engine. The nearest TMY cities to Grand Forks
include Fargo and Minot, North Dakota. The more severe weather
in Minot (similar latitude to Grand Forks) was chosen for the
annual simulations (Table 1).
TABLE
1
Minot, North Dakota TMY2 Weather Summary
Heating
Degree Days |
97.5%
Heating Design |
2.5%
Cooling Design |
9,407 |
-20ºF |
89ºF |
Average
energy rates were obtained from the serving utility for annual
cost and economic comparison calculations (Table 2).
TABLE
2
2003 Utility Rates – Xcel Energy
Electric
($/kWh) |
Natural
Gas Avg. |
Jun
- Sep |
Other
Months |
Average |
($/therm) |
0.0657 |
0.0578 |
0.0604 |
0.748 |
Base
Case Characteristics
A
base case home was simulated to provide a point of comparison
for annual energy use and payback analysis. This home used the
same geometry as the actual homes but with envelope construction
and equipment types normally used by builders in the Grand Forks
area (Table 3).
Building
Envelope
The
base case above-grade walls consist of 2x6 wood studs, 16 inches
on center to allow for R-19 batt insulation. The wall exterior
is OSB sheathing, building paper and vinyl siding. On the interior,
a vapor barrier of 6-mil polyethylene is installed behind the
gypsum wallboard to minimize moisture diffusion from the conditioned
space into the wall cavity. High-grade windows are the norm for
Grand Forks area builders. The modeled base case window is a
double-pane, vinyl framed, argon-filled, horizontal slider with
a low-e coating, providing a U-value of 0.34 and a Solar Heat
Gain Coefficient (SHGC) of 0.33. The assumed base case infiltration
is set at 5.0 ACH50 (1,227 CFM50).
The
basement (608 ft2) is upgradeable as a future living space with
two windows set below grade-level (in wells) for each of two
bedrooms. Cement basement walls are insulated to R-11 with 2x4
framing on the interior. The basement ceiling is uninsulated
and allows ample air communication with the living space above,
causing the basement zone to function as a conditioned space.
Equipment
Space
heating is provided by a gas furnace located in the basement,
with an efficiency of 78% AFUE. Cooling is provided by a 10SEER
air conditioner sized at 1.5 tons (18 kBtu) nominal. Set points
of 68ºF in winter and 78ºF in summer were assumed for
the DOE2 simulations. Ductwork is primarily located in the basement,
completely within the building’s air barrier. Supply ductwork
consists of uninsulated metal and return ducts are loosely constructed
pathways to the bedrooms and main body utilizing building cavities.
Total duct leakage is substantial in systems of this design but
leakage to outside is minimal and considered to be zero here.
Electric
water heaters (EF 0.88) are routinely used in this area according
to the builder. Natural gas price spikes in the last five years
was one reason sited for the continued use of electric water
heating in the Grand Forks area.
TABLE
3
Twin Home Specifications
|
Base
Case |
Phase
I |
Phase
II |
Conditioned
Area (with basement) |
1840
ft2 |
Same |
Same |
Above-grade
Walls |
R-19
Wood Frame |
R-19
Wood Frame |
R-15
Wood Frame + R10 sheath |
Basement
Walls |
R-11 |
Same |
Same |
Vented
Attic |
R-49 |
Same |
Same |
Windows |
U-0.34,
SHGC-0.33 |
Same |
Same |
Gas
Furnace |
60kBtu,
AFUE-78 |
60kBtu,
AFUE-92 |
60kBtu,
AFUE-92 |
Air
Conditioner |
1.5
ton, 10 SEER |
Same |
Same |
Thermostat |
Standard |
Programmable |
Programmable |
Ventilation |
None |
70%
efficient HRV |
70%
efficient HRV |
Water
Heater |
40gallon,
EF 0.88 Electric |
40gallon,
EF 0.62 Natural gas |
Tankless,
EF 0.83 Natural gas |
Lighting |
10%
Fluorescent |
85%
Fluorescent |
85%
Fluorescent |
Appliances |
Standard |
Energy
Star |
Energy
Star |
Infiltration
(ACH50) |
5.0 |
2.8 |
2.4 |
Phase
I Measures
Building
Envelope
Careful
attention to air sealing was the only difference over the base
case envelope design in Phase I. Upgraded casement-style windows
replaced the base case horizontal sliders to improve envelope
tightness. These argon-filled, vinyl-framed units are otherwise
identical to those assumed in the base case home with a 0.34
U-value and 0.33 SHGC. Blower door tests of the Phase I units
show an average leakage rate of 2.8 ACH50 was attained based
on 689 CFM50 as shown in Table 4 including the basement.
TABLE
4
Measured Phase I Envelope Tightness
Twin
Home Unit |
1 |
2 |
3 |
4 |
Average |
CFM50 |
737 |
728 |
574 |
716 |
689 |
ACH50* |
3.00 |
2.97 |
2.34 |
2.92 |
2.81 |
Notes:
*ACH50 = CFM50x60/volume (basement zone depressurized along with
main living space)
Equipment
The
78% furnace was replaced with a 92.6% AFUE, sealed combustion,
condensing gas furnace. Combustion air is drawn from outside,
completely sealing it from the inside space and minimizing the
chance of leaking combustion products to the conditioned space.
A programmable setback thermostat further reduces energy demand
with assumed swings of 5ºF in winter and 3ºF in summer
assumed for the DOE2 models. Savings were obtained by replacing
the electric water heater with a power vented natural gas model.
This is not an exceptionally efficient gas unit (EF 0.62) but
the power-venting feature provides a measure of combustion safety.
Recent
fluctuations in the price of natural gas complicate payback calculations
for both the furnace and water heater upgrades. The 2003 average
local rate ($0.748/therm) was obtained from the serving utility
for the economic calculations. In the ten years prior to 2000,
gas prices were relatively stable with a slight rise in the middle
of the year when heating demand is reduced. This trend has roughly
continued after 1999 but a substantial increase in winter prices
as seen in 2000-2001 (Figure 3) would have a considerable impact
on furnace upgrade savings, making the high efficiency unit look
much more favorable against the base case when prices increase.
For the gas water heater, on the other hand, increasing prices
would reduce its cost effectiveness relative to the base case
electric model, which is powered by an historically more stable
commodity that was 26% cheaper than the national average of $0.0813/kWh
in 2003 (EIA 2004).
Figure
3. North Dakota Natural Gas Pricing

Source: U.S. Energy Information Administration
(converted to $/therm from $/Mcf using estimated heat content
of 1,029 Btu/cubic foot)
Considerable
effort was focused on replacing incandescent fixtures with fluorescent
lighting, yielding a simple payback of 6.5 years. The typical
10% fluorescent fraction was increased to 85% with a combination
of linear and compact fluorescent light (CFL) fixtures. The only
locations with standard edison-socket fixtures are hallways,
bathrooms (with dimmers) and kitchen can lights (also with dimmers).
An
Energy Star dishwasher and horizontal-axis clothes washer provide
an annual savings of $37 by reducing electrically generated hot
water an estimated 10 gallons per day. The typical 60 gallons
of hot water use per day was reduced to 50 with an estimated
savings of 8 gallons from the horizontal-axis washer (Tomlinson
and Rizy 1998) and 2 more gallons from the dishwasher. Savings
from reduced water and detergent use are not included. The Energy
Star refrigerator saved an estimated $34 (1,100 kWh/yr vs. 450
kWh/yr) in electrical energy but $10 of this is lost per year
due to increased heating demand (approximately 14 therms).
A
heat recovery ventilator (HRV) mounted in the basement provides
controlled mechanical ventilation with an energy penalty estimated
at $45/year. The unit contains an 80-watt fan that introduces
75 CFM of outside air while exhausting a similar amount at a
heat transfer efficiency of 70%. Attempting to meet the new ASHRAE
62.2 standard (ASHRAE 1999) would require 42 CFM of continuous
ventilation. For these simulations however the old ASHRAE guideline
of 0.35ACH was used, calling for a continuous rate of 25CFM.
The HRV can operate either continuously or on an intermittent
20 minutes on, 40 minutes off cycle. Intermittent operation was
simulated to meet the old guideline.
Phase
II Measures

|
Figure
4. XPS foam at corner |
The
Phase II structures had only two new measures over those used
in Phase I: XPS foam board sheathing and tankless gas water heaters.
The use of rigid foam exterior insulation was considered early
in design discussions but was not implemented until Phase II
when plywood prices nearly tripled. This measure allowed the
construction of 2x4 walls, which were insulated with a blown
fiberglass product to achieve R-15. Two inches of extruded polystyrene
(XPS) (R-10) was installed except in areas where ½ inch
plywood bracing was required. These corner-braced areas received
1-1/2 inches (R-7.5) of insulated sheathing (Figure 4), making
up roughly 1/3 of the exterior wall area and resulting in an
average value of R-9.2 for use in the DOE2 simulation. The remaining
wall construction (siding, vapor barrier, etc.) matched the phase
I details.
The
unfaced XPS foam sheathing has a perm rating of 1.1 and is considered
a vapor retarder at the wall exterior. This is in addition to
the interior vapor barrier (6-mil poly) installed behind the
gypsum wallboard at the wall interior. Installation of two vapor
barriers in this manner leaves the wall vulnerable to moisture
accumulation should water unintentionally enter the cavity. There
will be only a slight ability for the wall to dry to the outside.
Another recommendation calls for removing the interior vapor
barrier and relying on two coats of latex paint on the interior
to limit diffusion from the conditioned space into the wall.
This option allows the wall to dry to some extent in both directions
but was not chosen by the builder.
Blower
door tests of the Phase II units show an average leakage rate
of 2.4 ACH50 was attained based on 598 CFM50 as shown in Table
5 including the basement.
TABLE
5
Measured Phase II Envelope Tightness
Twin
Home Unit |
1 |
2 |
3 |
4 |
Average |
CFM50 |
736 |
474 |
685 |
495 |
598 |
ACH50* |
3.00 |
1.93 |
2.79 |
2.02 |
2.44 |
Notes:
*ACH50 = CFM50x60/volume (basement zone depressurized along with
main living space)
An
instantaneous gas water heater with an energy factor of 0.83
provided an estimated annual savings of $42 over the phase I
gas model. Savings over the base case 40-gallon electric water
heater are estimated at $94, providing a 13-year simple payback.
The manufacturer claims a 20 to 25 year lifespan.
Ground
water temperatures in Grand Forks routinely reach below 40ºF
during the winter months, which would drop hot water output below
4 gallons per minute (GPM) at a 120ºF supply temperature
according to manufacturers performance data. The new homeowners
were notified that, while hot water would always be available,
some changes in usage habits might be required to allow for reduced
capacity. No homeowner complaints were reported during an exceptionally
cold 2003/2004 winter season in Grand Forks, which saw a new
all-time record low of -44ºF on January 30, 2004 (NOAA 2004).
Impromptu discussions with homeowners during envelope testing
(April 29-30, 2004) indicated general satisfaction with the units
to date.
Estimated
Annual Energy Use and Cost Comparison
Phase
I and Phase II energy measures were evaluated progressively by
adding one measure at a time to the base case home. Energy measures
were added in the order listed in Tables 6 and 7 to arrive at
estimated savings numbers for individual measures while allowing
for interaction of the building systems. Major construction components
or equipment were added first such as envelope measures and the
gas furnace. Hot water saving, Energy Star appliances were added
prior to the water heater upgrade to highlight their savings
with respect to electrically heated water.
One
row in Tables 6 and 7 shows the cumulative effect of all measures
added to the base case home. Estimated saving in this row includes
the cumulative effect of all measures incorporated together in
the DOE2 simulation. The heat recovery ventilator (HRV) is broken
out from the other measures to provide a meaningful simple payback
and first year cash flow figures for the other cumulative measures.
The HRV is considered an essential component for the indoor air
quality of these homes but comparing it to a base case home without
ventilation means no relative savings are attained thus this
measure is added in a separate row. With the exception of the
HRV all measures show a positive cash flow on a 6%, 30 year fixed
rate mortgage beginning in the first year.
TABLE
6
Economic Assessment of Phase I Measures
Energy
Measure |
Annual
Savings |
Installed
Cost |
Simple
Payback |
First
Year Cash Flow |
Reduce
infiltration to 2.8 ACH50 |
$90 |
$325 |
3.6 |
$68 |
Upgrade
to 92% direct vent furnace |
$52 |
$600 |
11.5 |
$11 |
Switch
to Programmable Thermostat |
$23 |
$130 |
5.7 |
$11 |
Upgrade
to Energy Star appliances* |
$61 |
$730 |
12.0 |
$12 |
Change
to EF-0.62 power vented water heater |
$52 |
$520 |
10.0 |
$16 |
Increase
from 10% to 85% fluorescent lighting |
$31 |
$200 |
6.5 |
$17 |
All
Measures |
$309 |
$2,505 |
8.1 |
$135 |
Heat
recovery ventilation @75cfm, 33% RTF |
-($45) |
$1,400 |
N/A |
-$134 |
All
Measures with HRV |
$264 |
$3,905 |
14.8 |
$1 |
Notes:
* Energy Star appliances include refrigerator, dishwasher and
h-axis clothes washer
- First year cash flow based on 30 year fixed rate mortgage with
interest rate of 6%, down payment of 5% and discount rate of
5%.
A general inflation rate of 3% per year was applied to the
upgrade cost of measures replaced at end of lifetime. Final value
of equipment
is determined by linear depreciation over lifetime.
Interest paid on mortgage is considered tax deductible using
a tax rate of 28%.
Energy costs escalate at 3% per year. A property
tax rate of 0.8% was applied to the energy upgrade cost and is
inflated at 3% per year.
Two
alternate measures used in Phase II were XPS foam board sheathing
and tankless gas water heaters, which were unfamiliar to the
builder and plumbing subcontractor. This meant a larger labor
premium was included in the installed cost than may be the case
in the future if they continue to be used. The XPS foam in particular
is being considered for other projects by the builder as plywood
prices continue to remain high in the area.
TABLE
7
Economic Assessment of Phase II Measures
Energy
Measure |
Annual
Savings |
Installed
Cost |
Simple
Payback |
First
Year Cash Flow |
Upgrade
walls to (R10 sheath + R15 FG batt) |
$72 |
$600 |
8.3 |
$31 |
Reduce
infiltration to 2.4 ACH50 |
$106 |
$325 |
3.1 |
$82 |
Upgrade
to 92% direct vent furnace |
$40 |
$600 |
15.0 |
-$1 |
Switch
to Programmable Thermostat |
$18 |
$130 |
7.2 |
$6 |
Upgrade
to Energy Star appliances* |
$60 |
$730 |
12.2 |
$12 |
Change
to EF-0.83 tankless gas water heater |
$94 |
$1,250 |
13.3 |
$10 |
Increase
from 10% to 85% fluorescent lighting |
$31 |
$200 |
6.5 |
$18 |
All
Measures |
$421 |
$3,835 |
9.1 |
$158 |
Heat
recovery ventilation @75cfm, 33% RTF |
-($43) |
$1,400 |
N/A |
-$134 |
All
Measures with HRV |
$378 |
$5,235 |
13.8 |
$24 |
Notes:
* Energy Star appliances include refrigerator, dishwasher and
h-axis clothes washer
- First year cash flow based on 30 year fixed rate mortgage with
interest rate of 6%, down payment of 5% and discount rate of 5%.
A general inflation rate of 3% per year was applied to the upgrade
cost of measures replaced at end of lifetime. Final value of equipment
is determined by linear depreciation over lifetime. Interest paid
on mortgage is considered tax deductible using a tax rate of 28%.
Energy costs escalate at 3% per year. A property tax rate of 0.8%
was applied to the energy upgrade cost and is inflated at 3% per
year.
A
performance comparison of the base case, and improved structures
is shown in Table 8. The increased heating design load in Phases
I and II over the base case is caused by the addition of 75 CFM
of ventilation introduced on a 20 minutes ON, 40 minutes OFF
cycle, which the base case does not have. The DOE2 model predicts
the need for very little cooling, however many new homes in this
area are being built with central air conditioning.
TABLE
8
Simulated Performance Comparison of Base Case and Improved Homes
|
Base
Case |
Phase
I |
Phase
II |
HERS |
85.2 |
89.7 |
92.2 |
Total Annual
Energy |
Cost |
|
Cost |
Savings |
Cost |
Savings |
|
$1,079 |
|
$815 |
25% |
$701 |
35% |
|
Cost |
Design
Load (kBtu/h) |
Cost |
Design
Load (kBtu/h) |
Cost |
Design
Load (kBtu/h) |
Heating |
$458 |
29.8 |
$366 |
33.4 |
$294 |
30.7 |
Cooling |
$15 |
9.9 |
$11 |
10.6 |
$10 |
10.3 |
Hot Water |
$245 |
|
$157 |
|
$116 |
|
Total |
$718 |
|
$534 |
|
$420 |
|
Summary
and Conclusions
A
total of eight twin home units (four each of Phase I and Phase
II) have been built to date on Selkirk Circle in Grand Forks,
North Dakota with the goal of achieving up to 50% energy savings
over the 1993 Model Energy Code. DOE 2 computer models of each
phase plus a theoretical base case house built to local minimum
standards were devised to determine energy savings and cost effectiveness.
Phase I and Phase II home models included input from envelope
airtightness testing results. Estimated combined gas and electric
utility savings ranged from 25% on Phase I homes to 35% on Phase
II homes over the base case.The increased utility savings of
Phase II over Phase I come from two energy saving measures unique
for this area: Extruded Polystyrene (XPS) foam sheathing and
tankless gas water heating. Simple paybacks for these measures
were 8.3 and 13.3 years respectively. Electric water heaters
are the current norm in the Grand Forks area, but with electricity
26% below the national average and natural gas prices on the
rise simple payback on the tankless model was relatively long.
In addition, fluctuating natural gas prices complicate the economic
analysis. Initial concerns of how the tankless water heater would
perform in this extreme climate were met with positive feedback
through the first winter, which was colder than normal, including
an all-time record low of -44ºF set at the Grand Forks International
Airport on January 30, 2004.The low water vapor permeance of
rigid XPS foam sheathing (1.1 perms) presents a dilemma in this
climate where an interior vapor barrier (usually 6-mil polyethylene)
is considered mandatory to minimize moisture diffusion from the
conditioned space into the wall cavity. The installation of two
vapor barriers leaves the wall vulnerable to moisture accumulation
should water unintentionally enter the cavity. One recommendation
calls for removing the interior vapor barrier and relying on
two coats of latex paint on the interior to limit diffusion from
the conditioned space into the wall. This option allows the wall
to dry to some extent in both directions but was not chosen by
the builder.
Acknowledgement
This
work is sponsored, in large part, by the Building America program
of the US Department of Energy (DOE), Office of Energy Efficiency
and Renewable Energy, Building Technologies Program under cooperative
agreement number DE-FC36-99GO10478. The authors appreciate the
encouragement and support from Mr. George James and Mr. Chris
Early, DOE program managers in Washington, DC. They are grateful
to FSEC colleagues Mr. Philip Fairey and Mr. Robin Vieira and
Building America collegues Dr. Joseph Lstiburek, Mr. Armin Rudd,
Mr. Brad Oberg and others for their many helpful suggestions
and comments over the past several years. Special thanks also
go to Mr. Kim Christianson of the North Dakota Department of
Commerce, Division of Community Service which provided funding
for building upgrades.Disclaimer: This report was prepared as
an account of work sponsored by an agency of the United States
government. Neither the United States government, nor any agency
thereof, nor any of their employees, makes any warranty, express
or implied, or assumes any legal liability or responsibility
for the accuracy completeness, or usefulness of any information,
apparatus, product, or process disclosed, or represents that
its use would not infringe privately owned rights. Reference
herein to any specific commercial product, process, or service
by trade name, trademark, manufacturer, or otherwise does not
necessarily constitute or imply its endorsement, recommendation,
or favoring by the United States government or any agency thereof.
The views and opinions of authors expressed herein do not necessarily
state or reflect those of the United States government or any
agencies thereof.
References
Parker,
D., P. Broman, J. Grant, L. Gu, M. Anello, R. Vieira and H. Henderson.
1999. EnergyGauge USA: A Residential Building Energy Design Tool.
Proceedings of Building Simulation '99, Kyoto, Japan. International
Building Performance Simulation Association, Texas A&M University,
College Station, TX.
Tomlinson,
J., D. Rizy. 1998. Bern clothes washer study final report. Oak
Ridge National Laboratory.
National
Oceanic and Atmospheric Administration, National Weather Service,
2004. Climatology web page, http://www.crh.noaa.gov/fgf/data/climate/gfkclmsea.
Energy
Information Administration, Average U.S. Residential Electric
Prices, Table 9.9, April 2004, http://www.eia.doe.gov
ASHRAE,
1999. ASHRAE Standard 62.2P-1989: Ventilation and acceptable
indoor air quality in low-rise residential buildings, American
Society of Heating, Refrigerating and Air-Conditioning Engineers.
Click
here for PDF Version |